Skip to content
Tutorials Center
My learning

Topics

Lesson 25 of 47 ยท Faults and Protection

Chapter 5 review: faults and protection

Review sequence components, fault current calculation, relays, breakers and coordination with a one-picture summary, a recap table, a breaker rating check and a ten-question quiz.

This chapter followed one event from start to finish. A short circuit appears; you model it with sequence networks; you compute the current; a relay compares it with a setting and a breaker opens. Each step has one or two formulas you should be able to write from memory and one idea you should be able to explain in a sentence. Use the picture and the table below as a checklist, try the calculator on your own numbers and then test yourself with the quiz.

Five numbered stages along a dotted track: fault, sequence networks, fault current, relay decision and breaker clearing
Chapter 5 in one picture: from a short circuit to a cleared fault.

What you will learn

  • Recall the key formulas and ideas of the chapter in one place.
  • Check a breaker rating against all fault types at a bus.
  • Find the weak spots to revisit before moving on to stability and control.

Recap table

Topic Key formula or rule Remember
Operator a a = 1โˆ 120ยฐ, 1 + a + aยฒ = 0 Rotates by 120ยฐ; the sum of the three unit phasors is zero
Decomposition V0 = (Va+Vb+Vc)/3, V1 = (Va + aVb + aยฒVc)/3, V2 = (Va + aยฒVb + aVc)/3 V0 is the average; neutral current is 3ยทI0
Sequence impedances Z1 = Z2 (static); Z0 of lines is about 2 to 4 times Z1 Delta windings block zero sequence
Three-phase fault I = E/(Z1 + Zf) Uses the positive network only
SLG fault Ia = 3E/(Z1+Z2+Z0+3Zf) Series; larger than three-phase when Z0 < Z1
LL fault Ib = โˆš3ยทE/(Z1+Z2+Zf) 0.866 of the three-phase current when Z1 = Z2
LLG fault I1 = E/(Z1 + Z2โ€–(Z0+3Zf)) All three networks in parallel
Asymmetry ip = ฮบยทโˆš2ยทI''k, ฮบ = 1.02 + 0.98e^(โˆ’3R/X) Sets making current and bus bar stress
Overcurrent relay t = TMSยทk/((I/Is)^ฮฑ โˆ’ 1) Coordinate with a CTI of 0.2 to 0.5 s
Distance relay Zone 1 about 80 to 85 %, zone 2 about 120 % with delay Impedance is proportional to distance
Differential relay Iop = abs(I1+I2) against Imin + slope ร— Ires Selective with no coordination; restraint stops false trips

Common misconceptions

"Fault level depends on the load." It depends on the source and network impedance.

"Sequence networks are separate systems." They are three views of one system, joined at the fault point in a way that depends on the fault type.

"The fastest relay is the best." A relay that is faster but less secure causes unnecessary outages. Speed, security and selectivity must be balanced.

Try it

The first example is a breaker rating check. Given the sequence impedances at a 33 kV bus, it calculates every fault type, finds the worst case and compares it with the breaker's interrupting rating. It is a calculation, using the formulas of the chapter.

Python Is the breaker big enough?

Press Run (or Ctrl + Enter) to see the result here.

Program input ยท what you'd type while the program runs

Type the answers before you press Run, one per line. Each time the program reads a line (with input()), it gets the next line from this box.

The second example is a quick drill. It picks a random fault type and asks which sequence connection applies. It is a self-test, not a simulator.

Fault connection drill

Check your understanding

Quick check ยท 10 questions

of 10 answered You scored / 10 ยท perfect!

  1. 1. Three phase currents are Ia = 120 A, Ib = 0, Ic = 0. What is the neutral current?

    In = Ia + Ib + Ic = 120 A, which equals 3 x I0 (I0 = 40 A).
  2. 2. Which sequence networks are connected in series for a single line-to-ground fault?

    All three carry the same current I1 = I2 = I0, so they are in series.
  3. 3. At a bus Z1 = Z2 = j0.05 pu and Z0 = j0.20 pu. Which fault current is larger, SLG or three-phase?

    Three-phase: 1/0.05 = 20 pu. SLG: 3/(0.05+0.05+0.20) = 10 pu. Z0 is larger than Z1, so the three-phase fault wins.
  4. 4. A relay with k = 0.14 and alpha = 0.02 is operated at I/Is = 10, TMS = 0.5. What is its operating time?

    t = 0.5 x 0.14 / (10^0.02 - 1) = 0.07/0.0471 = 1.49 s.
  5. 5. Why are zones of protection overlapped?

    Overlap around breakers guarantees coverage.
  6. 6. A bolted LL fault compared with a bolted three-phase fault (Z1 = Z2) is

    The LL current is sqrt(3)/2 = 0.866 of the three-phase value.
  7. 7. What does a differential relay compare?

    Kirchhoff's current law: in a healthy zone the sum of currents is zero.
  8. 8. An ungrounded system suffers a line-to-ground fault. The healthy phase voltages relative to ground become about

    With no return path the neutral shifts; the sound phases are at line-to-line voltage relative to earth.
  9. 9. What makes the first peak of a fault current larger than sqrt(2) times the rms value?

    The inductive network cannot change current instantly, creating a DC offset that decays with L/R.
  10. 10. Why should zone 1 of a distance relay stop short of the remote end?

    An overreaching zone 1 would trip instantly for faults on the next line, losing selectivity.

Summary

  • A fault is modeled with sequence networks, joined according to its type, then solved for I1, I2 and I0.
  • Fault current depends on network impedance, not on load; ground faults can exceed three-phase faults when Z0 < Z1.
  • DC offset raises the first peak to about ฮบยทโˆš2 times the rms value.
  • Protection is a chain of CT, relay, trip coil and breaker, coordinated with time or by zones and differential comparison.
  • The next chapter asks what happens when the fault is cleared too slowly, or when the disturbance is not a fault: stability and control.

Next: Chapter 6 overview: stability and control