Skip to content
Tutorials Center
My learning

Topics

Lesson 30 of 45 ยท Synchronous Machines

Chapter review: synchronous machines

Review alternators and synchronous motors with a V-curve summary picture, a table of the key formulas and a ten-question mixed quiz.

Alternators and synchronous motors share one model: an internal voltage E behind a synchronous reactance Xs. Everything in this chapter is that model viewed from two sides, as a generator pushing power out and as a motor taking it in.

Left: V-curves of armature current against field current for two loads with a dashed unity-power-factor line. Right: four formula chips for speed, EMF, power-angle and regulation
The V-curve and four formulas to remember.

Recap table

Idea Formula or rule Remember
Speed ns = 120 f / P no slip, exactly synchronous
Generated EMF E = 4.44 kw f ฮฆ Nph ฮฆ follows the field current
Equivalent circuit E = V + I (Ra + jXs) motor: V = E + I (Ra + jXs)
Regulation (E โˆ’ V) / V largest for lagging loads; can be negative for leading
Power angle P = 3 V E sin ฮด / Xs maximum at 90ยฐ
Starting damper cage, VFD or pony motor no starting torque on its own
V-curve current against field current minimum at unity power factor
Grid control prime mover sets P, field sets Q over-excited = supplies reactive power
Synchronizing same voltage, frequency, sequence, phase angle check with a synchroscope

Try it

Check the arithmetic on a new machine: a 11 kV, 2 MVA alternator with Xs = 40 ฮฉ and Ra = 2 ฮฉ. Change the numbers and the power-factor choices.

Python Regulation calculator

Press Run (or Ctrl + Enter) to see the result here.

Program input ยท what you'd type while the program runs

Type the answers before you press Run, one per line. Each time the program reads a line (with input()), it gets the next line from this box.

The second TryIt turns the motor formula around: given a load, how big must the load angle be, and how much margin do you have?

JS Load angle and pull-out margin

Press Run (or Ctrl + Enter) to see the console output here.

No output.

Check your understanding

Quick check ยท 10 questions

of 10 answered You scored / 10 ยท perfect!

  1. 1. A 4-pole alternator must produce 60 Hz. What speed must the prime mover provide?

    n = 120 f / P = 120 ร— 60 / 4 = 1800 rpm.
  2. 2. Which condition is NOT required before closing an alternator onto the grid?

    Voltage, frequency, phase sequence and phase angle must match. The power is set after connection.
  3. 3. A synchronous motor drives a constant load. Increasing its field current from the unity-power-factor point makes it draw

    Beyond the minimum of the V-curve the motor is over-excited and the armature current is leading and rising.
  4. 4. What limits the power a synchronous motor can deliver at a given excitation?

    P = 3 V E sin ฮด / Xs cannot exceed 3 V E / Xs.
  5. 5. For which load can an alternator show negative voltage regulation?

    A leading current magnetizes the machine, so the terminal voltage can rise above E.
  6. 6. Which of these is a typical cure for the lack of starting torque in a synchronous motor?

    Damper windings let the motor start as an induction motor before the DC field is applied.
  7. 7. An alternator is connected to a large grid. To deliver more real power you should

    Real power comes from the prime mover; field current mainly changes reactive power.
  8. 8. The synchronous reactance of an alternator combines

    Xs is a lumped model of leakage flux and armature reaction.
  9. 9. A synchronous motor with V = 3810 V, E = 4573 V and Xs = 15 ฮฉ carries 1 MW. Its load angle is about

    sin ฮด = P Xs / (3 V E) = 1 000 000 ร— 15 / (3 ร— 3810 ร— 4573) โ‰ˆ 0.287, so ฮด โ‰ˆ 16.7ยฐ.
  10. 10. An unloaded over-excited synchronous machine connected to a grid is called

    It draws no real power but supplies reactive power, which supports the voltage.

Summary

  • One model, E behind Ra + jXs, covers both the alternator and the motor.
  • The prime mover sets real power; the field current sets reactive power and voltage.
  • The load angle carries power, limited at 90ยฐ; the V-curve shows power-factor control.
  • Synchronous motors need an external way to start but offer constant speed and adjustable power factor.

Next: Chapter overview: special motors and drives