Lesson 34 of 38 · AC Circuits and Electromagnetic Waves

Transformers and Power Transmission

Learn how transformers step AC voltage up or down using mutual induction, the turns-ratio equations, and why high-voltage transmission wastes much less energy.

A power station might generate electricity at about 10 to 25 kV. It is sent hundreds of kilometers at 100 kV to 400 kV or more. Then it is stepped down again to 230 V (or 120 V) before it reaches your wall socket. A single device makes each of those changes possible: the transformer. It has no moving parts, it works with efficiency often above 98%, and it only works with alternating current.

This lesson explains how a transformer works, gives you the equations, and shows why high voltage makes transmission so much more efficient.

Mutual induction

Two coils wound on the same iron core are linked by the same magnetic flux. When the primary coil (with N_p turns) is connected to an AC source, its changing current creates a changing flux in the core. This flux passes through the secondary coil (N_s turns) and, by Faraday's law, induces an EMF there. This effect is called mutual induction. The iron core guides nearly all of the flux through both coils, and it is laminated (made of thin insulated sheets) to reduce eddy currents.

flowchart LR
  A["AC source"] --> B["Primary coil: N_p turns"]
  B --> C["Iron core carries changing flux"]
  C --> D["Secondary coil: N_s turns"]
  D --> E["Load"]

Energy travels through the shared magnetic flux, not through any wire between the coils.

The ideal transformer equations

The same flux per turn passes through both coils, so the EMF per turn is the same. The voltages are therefore in proportion to the turns:

Text
V_s / V_p = N_s / N_p

If N_s > N_p, the voltage is stepped up; if N_s < N_p, it is stepped down. For an ideal transformer there are no losses, so the power in equals the power out:

Text
V_p I_p = V_s I_s    so    I_s / I_p = N_p / N_s

Stepping the voltage up by a factor of 10 reduces the current by a factor of 10. There is no free lunch: a transformer changes voltage and current but not power.

Worked example

A phone-charger transformer steps 230 V down to 9.2 V and delivers 1.0 A on the secondary side.

  • Turns ratio: N_p / N_s = 230 / 9.2 = 25.
  • Output power: 9.2 × 1.0 = 9.2 W.
  • Primary current (ideal): 9.2 / 230 = 0.040 A.
Python Ideal transformer calculator

Press Run (or Ctrl + Enter) to see the result here.

Program input · what you'd type while the program runs

Type the answers before you press Run, one per line. Each time the program reads a line (with input()), it gets the next line from this box.

Real transformers

Real transformers are slightly less perfect. Losses include:

  • Copper loss: I² R heating in the windings.
  • Eddy-current loss in the core (reduced by lamination).
  • Hysteresis loss: energy used in repeatedly reversing the core's magnetization.
  • Flux leakage: some flux does not link both coils.

Efficiency is output power / input power. Large power transformers reach about 99%, small chargers somewhat less. A transformer's core gets warm, and large ones are cooled by oil.

Also remember that a transformer only responds to a changing flux. A DC supply produces constant flux and no secondary voltage, and the primary would simply overheat. That is why the electricity grid uses AC.

Why transmit at high voltage?

A power line has a small but non-zero resistance R_line. If it carries current I, it wastes power I² R_line as heat. To send a given power P = V I, a higher voltage V means a smaller current I = P / V, and the loss falls with the square of the current.

Worked example

Send P = 1.0 MW through a line of total resistance R_line = 5.0 Ω.

Transmission voltage Current I = P/V Loss I² R Fraction lost
10 kV 100 A 50 kW 5.0%
100 kV 10 A 500 W 0.05%

A tenfold increase in voltage cuts the line loss by a factor of 100. This is the central reason for step-up transformers at power stations.

Python Line loss at different transmission voltages

Press Run (or Ctrl + Enter) to see the result here.

Program input · what you'd type while the program runs

Type the answers before you press Run, one per line. Each time the program reads a line (with input()), it gets the next line from this box.

The table simplifies things: it treats the load power as fixed and ignores the small extra voltage drop along the line, which a real calculation would include. The lesson it teaches is still correct.

From power station to socket

flowchart LR
  A["Generator: about 20 kV"] --> B["Step-up transformer: 100-400 kV"]
  B --> C["Long-distance transmission lines"]
  C --> D["Step-down substations: 10-30 kV"]
  D --> E["Local transformer: 230 V or 120 V"]
  E --> F["Homes and factories"]

The grid steps voltage up for transmission and down for safety near people.

High voltage cannot be used in homes for safety reasons, so the voltage is stepped down in stages. Some long routes use high-voltage direct current (HVDC), which also needs transformers (and power electronics) at each end.

Impedance matching in brief

A transformer also changes the apparent size of a load. A load R_L on the secondary looks to the source like R_L (N_p / N_s)². Audio engineers use this to match a loudspeaker to an amplifier for good power transfer.

Common mistakes

  • Expecting a step-up transformer to give more power. It gives more voltage and less current.
  • Applying DC to a transformer.
  • Swapping N_p and N_s in the voltage ratio. The secondary is on top for the voltage.
  • Calculating line loss as V² / R, using the full transmission voltage. The line loss uses the voltage drop along the line I R, or I² R.

Check your understanding

Quick check · 4 questions

of 4 answered You scored / 4 · perfect!

  1. 1. A transformer has 200 turns on its primary and 50 turns on its secondary. The primary is connected to 120 V AC. What is the secondary voltage (ideal)?

    V_s = V_p × N_s / N_p = 120 × 50 / 200 = 30 V.
  2. 2. An ideal step-up transformer raises the voltage by a factor of 20. What happens to the current?

    Power is conserved, V I = constant, so the current falls by the same factor.
  3. 3. Why is electricity transmitted over long distances at high voltage?

    For a given power, a high voltage means a small current, and line losses scale with the square of the current.
  4. 4. A 2.0 MW load is supplied through a line of resistance 4.0 Ω at 40 kV. What is the power lost in the line (approximately)?

    I = 2.0×10⁶ / 4.0×10⁴ = 50 A; loss = 50² × 4.0 = 10 000 W = 10 kW.

Summary

  • A transformer uses mutual induction: a changing flux in the core links primary and secondary coils.
  • Ideal transformer: V_s / V_p = N_s / N_p and V_p I_p = V_s I_s.
  • Real transformers lose energy through winding resistance, eddy currents, hysteresis and leakage; efficiency is often above 95%.
  • Transformers work only with changing flux, so only with AC.
  • Line loss is I² R_line; raising the transmission voltage by a factor k cuts it by k².

Next: Electromagnetic Waves