Ir para o conteúdo

Lição 37 · Projects and Practice

PLC Programming Practice Exercises and Review

Practice PLC logic with graded exercises on timers, counters, edges, state machines, scaling and alarms. Each exercise has a runnable C model and hints for your own PLC code.

You learn PLC programming by building things. This lesson gives you graded exercises covering this part of the track: timers, counters, edges, sequences, HMI data, communication and fault handling. For each one, first write the logic in your own PLC tool or simulator (ladder or Structured Text), then compare with the C stand-in model here. No PLC runtime is available on this site, so the C programs are the runnable reference.

How to work: read the requirement, sketch inputs and outputs, decide which blocks you need (timer, counter, edge, state machine), write it, then test with a list of scenarios, including odd ones such as a button held down or both start and stop pressed.

Level 1: single blocks

Exercise 1: Delayed start with warning. When Start is pressed, a horn sounds for 3 s, then the motor starts. Stop turns everything off. (Hint: a TP or a TON for the horn phase, a latch for the motor.)

Exercise 2: Batch counter. Count bottles; when 6 have passed, pulse a gate output for 1 s and restart from 0. (Hint: CTU with the reset driven by its own done bit, one-shot for the gate.)

Exercise 3: Toggle button. One push-button starts and stops a lamp. (Hint: rising edge and a flip.)

Here are models of all three in one program:

C C stand-in: reference models for exercises 1 to 3

Press Run (or Ctrl + Enter) to see the result here.

Program input · what you'd type while the program runs

Type the answers before you press Run, one per line. Each time the program reads a line (with scanf or fgets), it gets the next line from this box.

Level 2: combining ideas

Exercise 4: Star-delta start (sequence). Start closes the main and star contactors, waits 5 s, opens star, waits 100 ms, closes delta. Never allow star and delta at once. (Hint: state machine plus interlocks on the outputs.)

Exercise 5: Two-pump alternation. Rework the tank project so the pump with fewer run hours starts first.

Exercise 6: Alarm with acknowledge. An over-temperature alarm at 90 degrees with a 2 s delay, 3 degree deadband and an acknowledge button. (Hint: alarm life cycle.)

C C stand-in: star-delta starter with mutual interlock

Press Run (or Ctrl + Enter) to see the result here.

Program input · what you'd type while the program runs

Type the answers before you press Run, one per line. Each time the program reads a line (with scanf or fgets), it gets the next line from this box.

Level 3: data and communication

Exercise 7: Scale and display. Convert a 4-20 mA signal (0-27648 counts for 0-16 mA above 4) into 0-250 degrees Celsius with a fault below 3.6 mA. Exercise 8: Pack a telegram. Send three values (a status byte, a 16-bit speed and a 16-bit temperature in tenths of a degree) in a 5-byte packet with a CRC, and parse it back. Revisit Modbus and I/O mapping.

C C stand-in: reference for exercise 8 (pack, check, parse)

Press Run (or Ctrl + Enter) to see the result here.

Program input · what you'd type while the program runs

Type the answers before you press Run, one per line. Each time the program reads a line (with scanf or fgets), it gets the next line from this box.

Level 4: faults and design

Exercise 9: Dual-channel guard door. Both channels of a gate switch must be closed to run; a mismatch longer than 200 ms faults. Reset only after both are closed again. (Model it on the safety lesson, and remember this is an exercise, not a certified function.)

Exercise 10: Find the bug. The ladder below has two defects. Find them before reading the answer.

TEXT
Rung 1:  | Start |---|/Stop|---( Motor )
Rung 5:  | Auto  |---|/Fault|--( Motor )

The answer: the output Motor is written in two rungs (a double coil, so Rung 5 overrides Rung 1), and Rung 1 has no seal-in contact so the motor stops as soon as Start is released. See good practice.

Exercise 11: Design review. Take the conveyor project and list ten things that could go wrong (sensor dirty, belt slips, encoder lost, cylinder stuck, air pressure low, jam, E-stop, power loss, wrong recipe, HMI disconnected) and write the program's reaction to each. This habit separates working programs from reliable ones.

Self-check with a quiz

Quick check · 4 questions

of 4 answered You scored / 4 · perfect!

  1. 1. In exercise 10, why does the motor stop as soon as Start is released?

    A momentary Start needs a seal-in contact from the Motor output in parallel with Start to hold the rung true.
  2. 2. Which block would you choose to count 6 bottles and then act?

    A count-up counter with PV = 6 raises its output when six rising edges have been counted.
  3. 3. What is the purpose of the dead time between star and delta contactors?

    A short gap prevents a short circuit between phases caused by both contactors being closed momentarily.
  4. 4. What is the best way to be sure a new program is robust?

    Reliability comes from testing odd and failing conditions, not only the expected sequence.

Summary

  • Practice in levels: single blocks, combined sequences, data and communication, faults and design review.
  • Always list scenarios, including unusual ones, before declaring logic done.
  • Model your ideas in a simulator or in C to check timing and states.
  • Typical bugs: double coils, missing seal-in, level instead of edge, missing timeout.
  • The C programs are stand-ins; write the real versions in your PLC environment.

Next: back to the PLC Programming track

Acompanhe seu progresso

Crie uma conta gratuita para marcar lições como concluídas e retomar de onde parou em qualquer dispositivo.